Class A vs. Class C FRP: Understanding Fire Ratings Before You Buy

The letter on an FRP spec sheet decides whether your walls pass inspection. Here's what ASTM E84 actually measures, what separates Class A from Class C, and how to tell which one your space needs.

Emco Industrial PlasticsSeptember 20268 min read

The short version

  • Class A and Class C are flame spread ratings from the ASTM E84 tunnel test. Lower numbers mean slower-spreading fire.
  • Class A means a flame spread index of 0–25. Class C is 76–200. All classes must keep smoke at 450 or below.
  • Building codes require better-rated finishes in exits and corridors than in rooms, and loosen the rules in fully sprinklered buildings.
  • FRP is sold almost entirely as Class A or Class C. If your space calls for Class A or Class B, buy Class A FRP.

Why the rating matters

FRP panels are chosen for moisture resistance and cleanability, so it's easy to treat them as a commodity and order whatever is cheapest. But FRP is an interior wall finish, and interior finishes are regulated by the building code for one reason: in a fire, the surfaces lining a room or hallway can carry flames toward the exits faster than people can reach them.

That's why an inspector may ask for the fire rating of your wall panels, and why installing the wrong class can mean tearing out finished walls. Standard FRP is usually Class C. Class A FRP uses a fire-retardant resin formulation and typically costs more. Knowing which one your project needs before you order saves money in both directions.

ASTM E84 in plain terms

ASTM E84, also published as UL 723, is the standard test for how fast flame travels across a building material's surface. It's often called the Steiner tunnel test after the long, narrow furnace it uses.

Infographic 1How the ASTM E84 tunnel test works
Diagram of the ASTM E84 Steiner tunnel test A 25-foot horizontal tunnel with the test specimen mounted face-down on the ceiling. Gas burners at the fire end ignite the specimen while air is drawn through at a controlled speed. Observers track how far the flame front travels along the 24-foot specimen over 10 minutes, and a light sensor in the exhaust measures smoke. Air in Smoke sensor 0 ft 6 12 18 24 ft 1 Specimen on the ceiling 24 ft × 20 in, face down 2 Flame front is tracked for 10 minutes 3 Gas burners at the fire end draft pulled through at a set speed 4 Light sensor in the exhaust measures how much smoke is made
Two numbers come out of the test. The flame spread index (FSI) is based on how far and how fast the flame travels. The smoke-developed index (SDI) is based on how much the smoke blocks the light sensor.

Both results are expressed relative to two reference materials. Inorganic reinforced cement board is set at 0, and red oak flooring is set at 100. So a material with a flame spread index of 25 spreads fire at roughly a quarter the rate of red oak, and a material rated 150 spreads it about one and a half times as fast.

From test scores to letter grades

The building code turns those index numbers into three classes. The smoke limit is the same for all of them. The difference is entirely in flame spread.

Class A

FSI 0–25

Smoke index 450 max. Required in exits and corridors of many public buildings.

Class B

FSI 26–75

Smoke index 450 max. Rarely offered in FRP, so Class A is used where B is required.

Class C

FSI 76–200

Smoke index 450 max. Standard FRP. Allowed in many rooms and sprinklered buildings.

Infographic 2Where FRP lands on the flame spread scale
Flame spread index scale with Class A, B and C bands A horizontal scale from 0 to over 200. Class A covers 0 to 25, Class B 26 to 75, and Class C 76 to 200. Above 200 is not permitted as an interior finish. Cement board is at 0 and red oak at 100. Class A FRP falls in the Class A band and standard FRP in the Class C band. A B C Not allowed 0 25 75 100 200 Flame spread index (ASTM E84) Cement board = 0 (reference) Red oak = 100 (reference) Class A FRP fire-retardant resin Standard FRP most commodity panels test here All three classes: smoke-developed index 450 or less
The gap between classes is big. The top of Class A (25) is one-eighth the top of Class C (200). FRP manufacturers target one end or the other, which is why Class B FRP is hard to find.
A rating belongs to a tested assembly

Many Class A FRP panels earn that rating when tested over a specific substrate, often gypsum board or another noncombustible backing. Installed over plywood or foam, the same panel may not carry the rating. Check the manufacturer's data sheet for the tested assembly and install to match it.

Where the code requires Class A

Most U.S. jurisdictions adopt the International Building Code (IBC), and some use NFPA 101, the Life Safety Code. Both use the same Class A, B and C system. In the IBC, the required class comes from a table (Table 803.13 in the 2021 edition) that looks at three things:

  • Occupancy group. What the building is used for: restaurant, school, hospital, warehouse and so on. Places where many people gather or can't evacuate on their own get stricter limits.
  • Location in the building. Exit stairways and exit passageways are held to the tightest standard, then corridors, then rooms and enclosed spaces.
  • Sprinklers. A fully sprinklered building is generally allowed a less restrictive class, often one step down.
Infographic 3Minimum wall finish class by occupancy
OccupancyFully sprinkleredNot sprinklered
ExitsCorridorsRoomsExitsCorridorsRooms
A-2 AssemblyRestaurants, bars, banquet hallsBBCAAB
B BusinessOffices, clinics, car washesBCCABC
E EducationalSchools, daycareBCCABC
M MercantileRetail, grocery storesBCCABC
I-2 InstitutionalHospitals, nursing homesBBBAAB
R-2 ResidentialApartments, dormitoriesCCCBBC
F FactoryManufacturing, food processingCCCBCC
S StorageWarehouses, cold storageCCCBBC
Class A requiredClass B or better (use Class A FRP)Class C or better (standard FRP OK)
Simplified from 2021 IBC Table 803.13. Footnotes, exceptions and less common occupancies are omitted. Your jurisdiction may use a different code edition or local amendments, so confirm with your building official.

A few patterns stand out:

  • Non-sprinklered exits and corridors are where Class A shows up most. Restaurants, hospitals and nursing homes need it in both.
  • Sprinklers change the answer. A room in a fully sprinklered restaurant can use Class C. The same room in a non-sprinklered building needs Class B, which in practice means Class A FRP.
  • Factories and warehouses are the most forgiving. In a sprinklered food plant or cold storage building, standard Class C FRP generally meets code throughout.

Which one should you buy?

Because FRP is almost always sold as either Class A or Class C, the decision comes down to one question: does any wall you're covering require Class A or Class B?

Infographic 4Choosing the right FRP in four steps
Decision flow for choosing Class A or Class C FRP Step 1, identify the occupancy group. Step 2, identify where the panels go: exit, corridor or room. Step 3, check whether the building is fully sprinklered. Step 4, look up the required class. If it is A or B, buy Class A FRP. If it is C, Class C FRP meets code and Class A also works. 1 What's the building? Find its occupancy group (A-2, B, F…) 2 Where do panels go? Exit, corridor, or room / enclosed space 3 Fully sprinklered? Sprinklers usually allow a lower class 4 Look up the class Use the table above or ask your code official Required class is A or B Buy Class A FRP Install over the substrate it was tested on Required class is C Class C FRP works Class A also works, at a higher cost
When one project has both kinds of walls, some buyers use Class A only in corridors and Class C in rooms to save money. Others order Class A throughout to keep one SKU and avoid mix-ups on site.

Common mistakes to avoid

  • Confusing flame spread with fire resistance. Class A is a surface rating. It is not an hourly fire-resistance rating like a 1-hour or 2-hour wall. FRP doesn't make a wall assembly fire-rated.
  • Assuming health code approval covers fire code. Health departments and USDA inspectors care that walls are smooth, durable, nonabsorbent and easy to clean. Fire rating is a separate requirement enforced by the building or fire official.
  • Ignoring the tested substrate. A Class A panel glued to plywood may not be a Class A installation.
  • Mixing stock on site. Class A and Class C panels can look identical. Keep them labeled and separated if you use both.
  • Waiting until inspection to ask. Confirm the required class with the architect, contractor or building department before ordering.

How Emco can help

Emco Industrial Plastics stocks FRP wall panels and matching trim and cuts panels to size in our Cedar Grove, NJ shop. Tell us what kind of building it is, where the panels are going, and whether it's sprinklered. We'll help you match the rating to your application and supply manufacturer data sheets for your submittals.

Call 973-239-0202

This article is general information to help you ask the right questions. It is not a code interpretation. Fire rating requirements depend on the code edition and amendments your jurisdiction has adopted, the building's construction and occupancy, and the product's tested assembly. The authority having jurisdiction makes the final call.